CJX2-E Series AC Contactor is suitable for circuits with the rated voltage up to 690V AC, 50Hz/60Hz and 250V DC and rated current of 6A and 9A for frequent making and breaking in starting and controlling of the AC motor. As machine interlocking contactor, combined with the auxiliary contact group, air delayer, and the thermal relay, it is combined into the electromagnetic starter.
Main Technical parameter
Parameter\Type: HC1(CJX2)-06E | HC1(CJX2)-09E
Rating working voltage. (V): 660 (690)
Rating working current (A): 380V AC-3 6 9 |
AC-4 2.6 3.5
Appoint heating current (A): 16 | 16
Max turn-on current(A): 380V 60 90 | 660V 72 108
Max turn-off current(A): 380V 48 72 | 660V 60 90
Three phases cage motors power which can be pulled AC3 (KW): 220V 1.5 2.2 | 380V 2.2 4 | 660V 3 5.5
Operation Frequency Time/h Electricity life: AC-3 1200 | AC-4 300
Electricitylife ( * 104 times): AC-3 100 | AC-4 20
Machinery life ( * 104 times): 1000
AC loop electricity loss (W): 2
DC loop electricity loss (W): 4
The section of connection guideline (mm2 ): 1.5
Matched fuse type: NTOO-16
Standard: GB-14048.4
The assistant contact head and assistant contact head group of contators
Use Type Rating working voltage(V) Rating working current(A) Control capacity Appoint heating current (A) Life
Turn on disport
AC-15 380 0.95 360VA 360VA 10 Same as main contact head
DC-13 220 0.15 33W 33W